|
|
|
FUSION TANKS LIQUID STORAGE SYSTEMS MODEL SPECIFICATION -ISOFUSION® GLASS FUSED BOLTED STORAGE TANKS |
|
1. GENERAL 1.1 Scope of work Supply and erect a Glass-Fused-to-Steel bolted sectional tank (s), including foundation, tank cover, tank structure and appurtenances as shown on the Engineer's drawings, and described herein.
|
|
All
labor, materials, plant, equipment and tools, as required for the
construction of the storage tank shall be included.
|
|
1.2
Qualifications
of Tank Supplier The Bidder shall offer new tank structures as supplies from a Manufacturer specializing in the design, fabrication and erection of factory applied Glass-Fused-to-Steel, bolted sectional tank systems. The Manufacturer shall own and operate its own production plant, fabricate and glass coat the tank plates at one location so as to provide full quality control responsibility over product.
|
|
1.3 Pre-qualification |
|
Pre-approved
tank manufacturers: |
|
The
Engineer's selection of factory applied Glass-Fused-to-Steel bolted
sectional tank construction for this facility has been based upon the
design criteria, construction methods specified, and optimum coating for
resistance to internal and external tank surface corrosion. Deviations
from the specified design, construction or coating details, shall not be
permitted.
|
|
Alternative
Glass-Fused-to-Steel bolted sectional tank systems, as provided by other
Manufacturers, will be considered for prior approved by the Engineer.
Manufacturers lacking the experience requirement will be considered if
the Manufacturer provides a satisfactory 5 year 100% Performance Bond in
lieu of evidence of experience and long term operations for tanks of a
similar application. |
|
Tank
suppliers wishing to pre-qualify shall submit the following to the
Engineer for consideration: |
|
a) b)
List
of tank materials, ancillary equipment and tank coating specifications. c)
List of five (5) tanks presently in service for a similar duty, of
size and character specified herein, operating
satisfactorily for a minimum of five (5) years, including reference
name, location, duty and year of supply. |
|
Only bids from tank suppliers who have successfully pre-qualified will be considered. 1.4 |
|
The
Engineer shall fully consider the life time cost implications of the
diverse range of tank sheet coatings and finishes available and reserves
the right to evaluate all bids based on life time costs (long term
operation, tank shut down time, coating and maintenance costs). Values
to be used in this evaluation will be at the discretion of the Engineer,
as detailed in this specification and bid tabulation form. |
|
As
a minimum the Engineer shall consider such cost implications over a 30
year operational period.
|
|
The
Engineer will add all such costs, dependent upon the type of tank
offered, to the Bidder's bid price to determine the effective low bid
for purposes of making the award.
|
|
1.5 Submittal Drawings and Calculation |
|
Construction
shall be governed by the Owner's plans and specifications showing
general dimensions and construction details, after approval by the
Engineer of submittal drawings prepared by the Manufacturer.
|
|
There shall be no deviation from these drawings and specifications, except upon written order or approval from the Engineer.
|
|
The Bidder
is required to furnish, for the review and approval by
Engineer,_____sets of construction drawings for all work not shown in
complete detail |
|
When
approved, two sets of such prints and submittal information will be
returned to the Bidder marked "APPROVED FOR CONSTRUCTION" and
these drawings will then govern the scope of work detailed thereon. The
approval by the Engineer of the tank supplier's drawings shall be on
approval relating only to their general conformity with the bidding
drawings and specifications and shall not guarantee detailed dimensions
and quantities, which remains the Bidder's responsibility. |
|
2.
DESIGN
CRITERIA |
|
Nominal
Diameter:
___________________ |
|
Sidewall
Height:
___________________ |
|
Nominal
Capacity:
___________________
US
Gallons/m |
|
High
Water Elevation:
___________________ |
|
Finished
Floor Elevations:
___________________
|
|
2.2 |
|
Option
a) The tank plate/sheet materials, design, fabrication and erection
of the sectional tank shall conform to the AWWA Standard "Factory-
Coated Bolted Steel Tanks for Water Storage" ANSI/AWWA |
|
Option b) Conformance
with AISC Design specification. |
|
Option c)
|
2.3 Design
Loads
|
Roof
Snow Load:
__________________
Roof
Live Load:
__________________
Imposed
Mechanical Load: __________________ |
|
Wind
Speed:
__________________
Shape Factor:
__________________
Allowable
Soil Bearing Capacity: __________________
|
|
Internal
Pressure:
__________________ Ins.WG/ |
|
|
|
2.4 Contents
Characteristics |
|
Contents
Description:
__________________ |
|
PH:
__________________ |
|
Temperature:
__________________ |
|
Concentration:
__________________ |
|
3. MATERIALS
3.1 Plates and
Sheets Plates
and sheets used in the construction of the tank shell, tank floor and
(optional) |
| Raw
materials delivered to the Manufacturer's plant shall be
tested/inspected to ensure compliance with the Manufacturer's
requirements for strength and chemical composition.
|
|
Test
Certificates and Certificates of Conformity shall be available
|
|
3.2
Horizontal Wind Stiffeners |
|
|
|
Wind
stiffener at top of tank shall provide a flat, horizontal, continuous
surface at tank rim level, compatible with any roof type that may be
included within the
|
|
Wind
stiffeners shall be steel, hot dipped galvanized-rolled steel angle or
web truss
types. 3.3 Bolt
Fasteners |
|
Bolt used tank lap joints shall be 1/2"
- 13 UNC-2A rolled thread with hot dipped galvanized coating. The
bolts shall have a minimum tensile strength of 113800 psi with shear
stress calculated at 0.25 of the tensile strength in accordance with
AWWA requirements and a minimum permanent set limit of 91000 psi. |
|
All
bolts for tank shell and roof (where applicable) shall be installed such
that the head portion is located inside the tank and the washer and nut
are on the exterior. |
|
All
lap joint bolts shall be properly selected such that threaded portions
will not be excessively exposed in the "shear plane" between
tank sheets. Also, bolt lengths shall be selected to achieve a neat and
uniform appearance. The torque values (as set down in the Manufacturer's
Builders Guide) shall not be exceeded during tank construction. All
lap joint bolts shall be designed to prevent rotation during tightening. 3.4
Bolt Head Encapsulation All
tank shell structure bolts shall have UV resistant polyethylene
encapsulation of the bolt head. |
3.5 Sealant
|
The
lap joint sealant shall be a one component moisture cured polyurethane
compound. The sealant shall be suitable for contact with potable water
and meet applicable FDA Title 21 regulations where necessary, as well
as, local health department guidelines for such use. |
|
The
sealant shall be used to seal lap joints, bolt connections and sheet
edges. The sealant shall cure to a rubber-like consistency and have
excellent adhesion to the glass coating, have low shrinkage, and be
suitable for interior and exterior exposure. The sealant shall be Sika 1A or suitable, equivalent materials approved by the Engineer. EPDM or Neoprene gaskets and tape type sealer shall
not be used other than for Note:
FDA title 21/ NSF registered material shall not be a requirement
for |
|
4. GLASS COATING |
|
4.1 Surface
Preparation |
|
Sheets
shall be steel ½ grit-blasted
to a silver gray finish on both sides to the equivalent of SA2 ½ or
SSPC-10. Sand blasting and chemical pickling of steel sheets is not
acceptable. |
|
The surface anchor pattern shall be not less than 1.0 mil. |
|
4.2
Cleaning |
|
Immediately
after fabrication and grit blasting and prior to application of the
coating materials, all sheets shall be thoroughly cleaned by an alkali
wash and a hot rinse process providing rust inhibition followed by heat
drying.
|
|
4.3
Coating - Double Cost, Single Fire Process |
|
All
sheets shall receive one coat of nickel rich pre-coat to both sides
followed by heat drying. |
|
A
coat of cobalt rich glass slip shall be continuously applied by
reciprocating sprays to both sides of the sheet followed by heat drying,
After inspection |
|
sheets
shall then be fired through the furnace at minimum 1500°
F. Sheets with visual spray or glass defects shall be rejected at this
point. |
|
The
resulting melting and bonding of the cobalt rich, silica glass frit
formulation to the steel shall form a composite glass surface having
general acid/alkali resistance to solutions in the range pH 3 to pH 9. |
|
At
all times firing of the coating shall be in strict accordance with the
Manufacturer's quality process control procedures, including firing
time, furnace humidity and temperature control. |
|
Internal
tank sheet color to be Cobalt Blue (Munsell 5 PB 2/4, RAL 5013, BS 4900
20-C-40) unless otherwise stated with external sheet color cobalt Blue
or Dark Green (Munsell 2.5GY 2/2, RAL 6006, BS 4900 12-B-29). |
|
Sample
tests shall be carried out by the Manufacturer to ensure that the
Enamel/Glass shall meet the physical properties and chemical resistance
characteristics of the Manufacturer's published specification.
|
|
4.4
Inspection |
|
Inspection
procedures shall be carried out within the Manufacturer's plant under
ISO 9001 Quality Systems. |
|
Finished
sheets shall be inspected for coating thickness using an approved
instrument suitable for a measurement range of 0-20.0 mils, The
Instrument shall be regularly checked against the Manufacturer's
approved calibration standard. |
|
The
average thickness of the glass coating shall be maintained in the range
from 7.1 mils to 11.0 mils. At no point shall the thickness of the glass
coating be less than 7.1 mils. Plates having an average thickness
outside of these limits shall be rejected. |
|
Electronic
color control shall be used on the external surface to ensure that color
uniformity is achieved within the Manufacturer's specified parameters.
Sheets of a color outside of these limits shall be rejected. |
|
The external/non-contact surfaces of all sheets shall be inspected visually under good daylight (or equivalent lighting) for defects in the glass coating, any sheet having visible defects larger than 0.04 inch shall be rejected. Any sheet having more than 3 visible lesser defects per square yard of external surface shall be rejected. Any visible defects on the external surface of accepted sheets shall be repaired to the Manufacturer's approved procedure.
|
|
An
electrical Holiday detection test shall be performed to the contact
surface of every sheet in accordance with ISO 8289. The test instrument
shall be a 9v detector having 90,000 ohms resistance using 3% sodium
nitrite solution as the approved wetting agent. |
|
|
|
Sheets
having any discontinuities in the glass contact surfaces shall be
rejected.
|
|
Only finished sheets with glass continuity defects
the contact surface |
|
An owner representative may be present during these inspection procedures at their own cost.
|
|
4.5
Sheet
Edges |
|
All
sheet edges, bolt holes and pre-formed openings shall have a limited
glass cover (Glass-Fused-to-Steel materials perform to their optimum
where the glass is in compression - sheet edges are often in tension).
|
|
A
further factory applied coating of a quick drying, single component,
stabilizing finish, reinforced with flat self leafing glass flake, shall
be applied to all sheet edges to provide additional protection during
transport and site storage. Further protection shall be provided by the
correct use of the approved sealants during construction, application of
the sealant and the profile detail of the sealant beading (internal and
external) to be strictly in accordance with the Manufacturer's Building
Manual. |
|
4.6 Packing All
finished sheets shall be handled within the manufacturing plant using
suction pads. |
|
All
approved sheets shall be protected from damage prior to packing for
shipment. |
|
Heavy
paper sheets shall be placed between each panel to eliminate sheet-to- |
|
Individual
stacks of panels will be wrapped in heavy duty black plastic and |
|
5. ERECTION |
|
Field
erection of the Glass-Fused-to-Steel, bolted-steel tank shall be in
accordance with the procedures outlined in the Manufacturer's Building
manual and performed by an Authorized Distributor of the tank
Manufacturer, regularly engaged in erection of these tanks or a suitably
qualified specialist sub contract builder under the control and
supervision of the Authorized Distributor.
|
|
The
floor design if required, shall be Glass-Fused-to-Steel. Bolted panels
shall be placed over a compacted sand base contained by a concrete ring
wall.
|
|
Leveling
of the starter ring (or first full ring) shall be required. The maximum
differential elevation within the ring shall not exceed 0.11 inch, nor
exceed 0.04 inch within any 3ft. length.
|
|
Specialized
erection jacks and building equipment shall be used to erect the tanks -
low profile, open topped tanks up to 25 ft. high may be built using the
stacking method (built from foundations upwards) using suitable plant
and equipment.
|
|
Particular care shall be taken in handling
and bolting of the tank panels and members to avoid abrasion of the
coating system. All surface areas may be visually inspected by the
Engineer during construction and prior to liquid tests.
|
|
An
electrical Holiday test shall be performed on all contact surfaces of
the tank shell plates during erection using a nine (9) volt leak
detection device having 90,000 ohms resistance. Any electrical leak
points found on the contact surface shall be repaired in accordance with
the Manufacturer's published touch up procedure. After completion of
tank build, but before tank cleaning and hydraulic testing the Engineer
shall sign the Manufacturer's standard Certificate of Satisfaction
issued by the Authorized Tank Distributor. |
|
No
backfill or mechanical loads shall be placed on the tank sidewall
without prior written approval and design review by the tank
Manufacturer. Any backfill shall be placed according to the instructions
of the Manufacturer.
|
|
6. APPURTENANCES |
|
The
ancillary items of equipment shall be installed as shown on the plans
and as detailed in these specifications. They may include, but are not
restricted to the following items: |
6.1
Outside Tank Ladder
|
An outside
ladder with safety cage beginning a minimum of 8 ft. above the level of
the tank bottom and at the location designated. Outside ladder and cage
shall meet Occupational Health and Safety Administration (OSHA 29 CF3
part 1910) requirements.
6.2 Inside Tank Ladder
(Optional) |
|
An inside
tank ladder, if required, shall be installed below the roof hatch and
|
|
Alternatively, internal ladders constructed from Fibre Reinforced Plastic (FRP) may be deemed acceptable.
|
|
6.3 Shell
Access Manway |
|
One manway having a minimum opening size of 24" shall be provided in the middle of the tank sheet clear of any vertical and horizontal bolt seams. The manway shall include a reinforcing frame and cover plate with a hinged support for cover removal. The manway shall comprise cover plate sealed with an approved gasket system. |
|
6.4 Inlet
and Outlet Connections |
|
Inlet,
outlet and overflow connections shall conform to the sizes specified on
the submittal drawings and shall be located so as to avoid vertical and
horizontal bolt seams. Positions shall be agreed between the Engineer
and the Authorized Tank Distributor. |
|
Where
connections are shown to pass through tank panels, they shall be |
|
a) Field located, saw cut, (acetylene torch
cutting, grinding, or welding is not permitted) and shall utilize an
interior and exterior flange assembly. |
|
b) Pre-cut
by the tank Manufacturer prior to glass application. |
|
Sika
IA joint sealant (or similar
approved) shall be applied on any cut panel edges or
bolt connections. |
|
Inlet, outlet and overflow connections shall be hot-dipped galvanized
steel. |
|
6.5 Cathodic
Protection |
|
Cathodic
protection may be supplied at the request of the Owner or
the Engineer, who should seek the approval of the Tank Manufacturer
or his Authorized Distributor regarding the fitting of this equipment to the structure.
|
|
7. FIELD
TESTING |
|
7.1 Leak Test |
|
Following
completion of erection, low voltage electrical testing and cleaning of
the tank, (and making due allowance for the full curing of the sealants)
the structure shall be tested for liquid tightness by filling to its
overflow elevation for a 24 hour period. |
|
Any
leaks disclosed by this testing shall be corrected by the erector in
accordance with the Manufacturer's recommendations. |
|
Water
required for testing shall be furnished by the Owner at the time of tank
erection completion, and at no charge to the Authorized Tank
Distributor. |
|
Disposal
of test water shall be the responsibility of the Owner. |
|
Labor
and equipment necessary for tank testing shall be included in the price
of the tank. |
|
Upon
satisfactory completion of the 24 hrs. hydraulic leak test the Engineer
shall sign the Manufacturer's Certificate of Satisfaction issued by the
Authorized Tank Distributor. 8. DISINFECTING |
|
8.1 Sika 1A |
|
Disinfection
shall not take place until polyurethane joint sealant is fully cured (10
to 12 days @ 73 F 50% Relative Humidity). |
|
The
tank shall be disinfected by chlorination in accordance with AWWA-C 652
- 92 section 4. Parts 1 and 2.
|
|
8.2 For tanks requiring disinfection but where other
sealants are utilized due to severe operating conditions within the tank
or the nature of the contents dictates the use of other suitable sealing
materials, a full written disinfection method statement shall be issued
by the Manufacturer for the approval of the Engineer. |
|
9.
WARRANTY |
|
9.1 One
Year Warranty |
|
If
within a one year period from the date of delivery to the job site the
tank, or any part there of, shall prove to be defective by reason of
poor design, materials or manufacture upon examination by the
Manufacturer or his Authorized Distributor the Manufacturer will supply
an identical or similar replacement part F.O.B. the Manufacturing plant
or at it's own option will repair the part.
|
|
9.2 Five
Years Warranty If within a
five year period from the date of delivery to the job site the Glass- 10. CONSTRUCTOR'S RESPONSIBILITY The constructor shall erect the structure
free of defects in workmanship. This responsibility shall be in effect
for a period of 12 months from the date of acceptance but no more than
12 months from the date of completion of installation by the
constructor. Any faulty workmanship found within those periods shall be
repaired by the constructor.
|
|
11.
INSPECTION |
|
On
or near the one year anniversary date of tank installation (but not more
than 14 months from date of delivery of tank materials to job site) the
Manufacturer's Authorized Distributor shall make a visual inspection of
the tank interior coating and appurtenances, tank exterior coating and
appurtenances, and the immediate area surrounding the tank. |
|
The
Manufacturers Standard Inspection Report Form shall be completed and be
filed with the Owner and the Authorized Tank Distributor at this time. |